Fig. A: Rules for Notching and Boring
Studs

Click image to enlarge.
But you can’t just drill and saw away. There are rules you have to follow for drilling and notching studs. Some rules help ensure the structural integrity of a wall. And others are aimed at protecting pipes and wires that could be damaged by screws, nails and other fasteners driven into a wall.
You Gotta Keep the Structure Strong
There are LOTS of building codes dictating just how large
a hole or notch you can cut (Fig. A).
The boringly (ha!) technical yet important rules are:
-
Holes in bearing wall studs (exterior and interior walls that bear the weight of the roof and/or other stories above) may not exceed 40 percent of the width of the stud.
-
Notches in bearing wall studs may not exceed 25 percent of the stud’s width.
-
Holes in non-bearing walls can’t exceed 60 percent of their width.
-
Notches in non-bearing walls can’t exceed 40 percent of their width.
-
The edge of a hole must be at least 5/8 in. from the edge of a stud.
Building codes allow you to drill bigger holes and cut bigger notches in non-load bearing walls (like the one on the left) than in load-bearing walls (right).
To appease the plumbing gods, the codes have made at least one notable exception: In bearing walls you can bore 60 percent size holes—as long as you double up the studs and don’t drill through more than two successive pairs of these doubled-up studs (Fig. A). This allows you to run a short section of “drain, waste, vent” (DWV) pipe through a 2x4 wall without beefing up the whole wall to 2x6 dimensions.
There are other, less specific guidelines: When possible, notch a stud near the top, rather than the bottom. Don’t locate holes and notches near large or loose knots, and don’t group too many in the same area of the stud. Finally, notch only when necessary; holes weaken it less than notches.
In areas subject to high winds, earthquakes or tornadoes, maintaining wall strength is particularly important. Furthermore, studs with too much “meat” removed tend to bow and warp. Your building inspector will be on the lookout for overzealous notching and boring, so follow the rules.
In reality, few walls ever out-and-out collapse during everyday duty from being riddled with too many holes and notches. But there are LOTS of cases in which unprotected or inadequately protected pipes and wires have been nicked and punctured by screws and nails. Any plumber or electrician will tell you that’s what you REALLY need to watch out for!
Protect Those Wires and Pipes
The National Electrical Code requires holes containing
non-metallic sheathed cable (one brand is Romex) or flexible metal-clad cable (the type
you buy with the wires already in it) be set back 1-1/4 in. or more from the
edge of a stud (Fig. A) to protect the wires from nails and
screws. (The 1-1/4 in. screws and nails used to secure 1/2-in. drywall
penetrate the studs about 3/4 in.) Most electricians keep their inspector happy
by drilling 3/4-in. holes dead center on a 3-1/2 in. wide stud. This gives them
a hole large enough to run two electrical cables and leave 1-3/8 in. of
protective wood on each side. If they need to run more wires, they’ll
drill more holes directly above the others. If a hole comes any closer than
1-1/4 in., your inspector will make you install a 1/16-in. thick protective
metal plate (Fig. A). Available in 3-in. and longer lengths,
the plates can be found at home centers and hardware stores for about 20¢
and up.

Click image to enlarge.
Use a right angle drill with hole saw bits for boring large holes. Keep the holes centered on the studs and a consistent height off the floor.
The mechanical codes for plumbing and heating, ventilation and cooling (HVAC) systems also dictate that holes containing pipes be set back 1-1/4 in. from the edge of a stud to protect the pipes from fasteners. Those that come closer need to covered by metal plates; for big pipes, use a long protective plate.
Fig. C
Click image to enlarge.
Angled holes are tough to pull wires through because the cable catches on the sharp edges.
Electricians and plumbers spend lots of time drilling big holes, so they know a few tricks to make the job easier (or avoid it altogether).
Tips for Less Drilling and Notching-
Before beginning any project, plot out exactly where large pipes and ducts will run and determine how you’ll get them there.
-
Wherever possible, run large pipes and ducts vertically into unfinished attics or basements, then install elbows and run the pipe or duct horizontally below the floor joists or above the ceiling joists.
-
Build 2x6 stud walls where DWV pipes and holes exceed the limits shown in Fig. A.
-
Rent a right angle drill and use Selfeed or hole saw bits for boring large holes (Fig. B). The right angle drill allows you to drill holes square to the stud face. Holes drilled at an angle will wind up oval and therefore larger.
-
Drill holes at least 1/4 in. oversize, especially for hot water pipes. If you don’t, they’ll make annoying sounds as they expand, contract and rub along studs.
-
Simpson (800-999-5099; www.strongtie.com) and other companies manufacture “stud shoes,” wrap-around, stud reinforcer plates (Fig. A). Ask your inspector if they are permissible in special situations.
-
When boring electrical holes, keep them square to the stud for easier wire installation, or pulling. This may seem trivial, but angled holes like those shown in Fig. C “catch” the wire and keep you from pulling wire through more than two or three studs at a time. Holes in a line (Fig. D) let you pull wire through an entire wall length of studs at one time.

Click image to enlarge.
Holes square to the face of a stud are easy to pull wires through.